HMI Screen Selection: Size, Brightness and Touch Type

The HMI That Was Too Small: Operator Interface Design on the Shop Floor

A 5-inch HMI on a machine in a noisy plant. The operator couldn’t read the screen from 1 meter away. The fault messages were tiny. The buttons were small — the operator pressed the wrong one. The customer asked for a bigger HMI. This is about HMI sizing and design for the shop floor, not about the HMI hardware.

The sizing rule

HMI size Viewing distance Use for
3.5 inch 0.5 m Small panels, setup only
5 inch 0.8 m Simple machines, single function
7 inch 1.5 m Standard machines, operator interface
10 inch 2.5 m Complex cells, multiple stations
15 inch 4 m Andon, overview screens

Our machine’s operator stood 1.5 m from the HMI. The 5-inch screen was too small. We upgraded to a 7-inch. The text was readable from 1.5 m.

The screen design

Even a big HMI is useless if the screen is poorly designed. The operator needs:

  • A main screen: machine status (running/stopped/fault), cycle count, part counter. No sub-menus for the primary info.
  • A fault screen: clear fault message in plain language. “Air pressure low at station 3” not “E1023”. A reset button.
  • A setpoint screen: cycle time, temperature, speed. Accessible but not on the main screen (prevent accidental changes).
  • A maintenance screen: PM intervals, alarm history, sensor diagnostics. Locked with a password.

What we changed

1. Bigger HMI. 7-inch, not 5-inch. The text is 14-point (not 10-point). The fault messages are red on yellow (high contrast).

2. Big buttons. The start/stop buttons are 50 mm on the screen. The operator doesn’t need to look closely. Emergency stop is a physical button, not on the screen.

3. Plain-language faults. The HMI shows “Clamp cylinder not extending — check air pressure” instead of “I:0/0 fault.” The operator knows what to check.

4. Physical buttons for safety. Start, stop, and e-stop are physical, not on the HMI. The HMI is for status and setpoints. Safety-critical actions are hardwired.

The viewing angle

An HMI in direct sunlight needs a bright display (500+ nits). An HMI in a dark machine shop can be dimmer. We mounted the HMI at eye level (1.5 m from floor), tilted 15 degrees toward the operator. The anti-glare coating reduces reflections. The customer could read it from the normal working position.

The HMI rule: Size the HMI for the viewing distance (7-inch for 1.5 m). Use big buttons and plain-language faults. Keep safety actions (start, stop, e-stop) as physical buttons. The HMI is for information, not for replacing hardwired safety. A 5-inch screen in a noisy plant is a frustration, not an interface.